Dynalco SW-200B Speed Switch發(fā)動(dòng)機(jī)超速保護(hù)開關(guān)
engine overspeed protection Switch
Dynalco SW-200B提供可靠的發(fā)動(dòng)機(jī)超速保護(hù)。它有三個(gè)可調(diào)繼電器設(shè)定值:第一個(gè)是超速。兩個(gè)輔助設(shè)備的用途包括曲柄斷開、發(fā)電機(jī)磁場閃爍和速度監(jiān)測。設(shè)定值是現(xiàn)場可編程的,可以在不超速的情況下進(jìn)行測試。外殼是密封的。SW-200B速度開關(guān)提供三個(gè)可調(diào)繼電器設(shè)定點(diǎn),用于發(fā)動(dòng)機(jī)超速保護(hù)、曲柄斷開、發(fā)電機(jī)磁場閃爍和速度監(jiān)測,并具有完全的現(xiàn)場編程能力。
Dynalco SW-200B provides reliable engine overspeed protection. It has three adjustable relay setpoints: number one is overspeed. Uses for the two auxiliaries include crank disconnect, generator field-flashing, and speed monitoring. Setpoints are field-programmable and can be tested without overspeeding. Housing is gasketed and sealed.SW-200B Speed Switch provides three adjustable relay set points for engine overspeed protection, crank disconnect, generator field flashing, and speed monitoring with full field-programming capability.
Dynalco SW-200B Speed Switch
Dynalco SW-200B Speed Switch
Inputs: Senses signal frequency from magnetic pickup or AC signal generator.
Outputs: Three relays (speed setpoints) and one 0-1 mA proportional DC output.
Field-programmable: Four DIP switches provide a variety of frequency input and overspeed relay logic configurations. Also three trim potentiometers to adjust setpoint range, and one potentiometer to adjust the proportional output.
Circuit: High-reliability. Virtually immune to electrical and RFI noise.
Test/Verify: Permits testing without overspeeding.
Case: Sealed and gasketed.
資料下載:
SW-200B Data Sheet
SW-200B Manual
Product Code: SW-200B
SW-200B Speed Switch
2-Year Warranty
規(guī)格參數(shù):
??
Inputs: Senses signal frequency from magnetic
pickup or AC signal generator.
??
Outputs: Three relays (speed setpoints) and
one 0-1 mA proportional DC output.
??
Field-programmable: Four DIP switches provide
a variety of frequency input and overspeed
relay logic configurations. Also three trim
potentiometers to adjust setpoint range, and
one potentiometer to adjust the proportional
output.
??
Circuit: High-reliability. Virtually immune to
electrical and RFI noise.
?? Test/Verify: Permits testing without overspeeding.
?? Case: Sealed and gasketed.
SPECIFICATIONS
Environment
?? Temperature: (storage & operation)
–40oF to +185oF (–40oC to +85oC).
?? Vibration:
?? MIL STD 810C, Method 514.2, Curve P,
Procedure V.
?? MIL STD 202F, Method 201A (10-55 Hz,
continues displacement of 0.06 in. P-P).
?? Screws on all access holes are predrilled
for safety wire.
?? Humidity: SAE J1211, paragraph 4.2.3., figure
3A; 95% relative humidity at +150oF (+66oC).
?? Dust: MIL STD 810C, Method 510.1, Procedure 1,
Steps 1,4,5,6. (175 ft/min velocity: 0.3 g/ft3 density;
<176 M average particle size).
?? Sealing: Can open and reseal case without
damaging watertight integrity. O-ring sealed
access holes for setpoint and proportional output
adjustments. Case complies with NEMA Standard
250, Types 3, 4, 12, and 13.
?? Moisture protection: Component board entirely
dip-coated with moisture repellent sealant.
Functional
Power: 9–40 Vdc, 300 mA maximum.
Withstands:
?? 800 volts peak reverse voltage.
?? 80 volts peak forward voltage, 0.1
second maximum duration.
?? 350 volts peak forward voltage, 1 milli-second
maximum duration.
Standard signal frequency ranges: 0–11,200, 0–
5,000, 0–1,000Hz. Field-selectable using built-in DIP
switches.
Input Signal:
?? Minimum signal requirement: 50 mVrms
at frequencies below 1 kHz; 0.4 Vrms at 11
kHz.
?? Maximum signal: 70 Vrms.
?? Minimum input resistance: 10 kW.
|